Trane IPAK I & II - Space Temperature Invalid Active or RTM Sensor Failure

3 months ago
5

Trane IPAK I & II - Space Temperature Invalid Active or RTM Sensor Failure.

Intellipak nuisance diagnostics / warnings. Intellipaks frequently don’t use a single space sensor to control the RTU. Find the appropriate terminal block for the space temp sensor input. If there’s no field wire pulled and landed on the appropriate points and you verify there shouldn’t be one, you can simply install a 10K ohm resistor across these two points. Your points may be different from model to model. If you install the 10K ohm resistor on the appropriate points, the space temp should read 77°F at all times.